Compare two radiator schedules for the same room
See how two quotes can match on the front page and disagree in the living room or bedroom.
Start with the same design assumptions
Copy the assessed heat loss for each room and the intended room temperature. Make a row for every room in the survey, even if a quote says to retain the existing radiator. Record the design outdoor temperature and ask the installers to reconcile different room-loss figures before treating a difference in emitter size as a saving.
A two-room worked comparison
Both quotes below assume 55°C flow, 45°C return and a 20°C room, giving ΔT30. All outputs use the Softline brochure factor 0.515. Wattages in the quote columns are combined ΔT50 catalogue ratings.
| Room / loss | Quote A | Quote B |
|---|---|---|
| Living room · 1,200 W | 2,000 → 1,030 W 170 W short | 2,400 → 1,236 W 36 W spare |
| Bedroom · 750 W | 1,600 → 824 W 74 W spare | 1,400 → 721 W 29 W short |
Ask about the room with the gap
Quote B’s combined output is 1,957 W against combined losses of 1,950 W. Its bedroom still has a 29 W shortfall at the stated conditions. Extra living-room output cannot be assigned to the bedroom on paper. Ask the installer to confirm the bedroom’s design assumptions and provide the selected product’s output. If Quote A assumes 750 W bedroom loss and Quote B assumes only 650 W, enter the two values separately. The same 721 W becomes 71 W spare against Quote B’s own figure. Ask which survey or room temperature explains the 100 W difference.
Compare your quotes