What to ask when a room heat loss is missing
Find the missing value in a quote and give the installer a question they can answer.
A whole-house figure leaves a question open
A quotation lists a heat loss of 6.4 kW and shows a new upstairs landing radiator. Those details alone do not establish whether an existing bedroom emitter covers that bedroom on the design day. The Energy Saving Trust’s installer guidance describes a room-by-room assessment using building measurements, insulation and ventilation details.
Record the missing fields explicitly
Suppose the bedroom schedule shows a retained, 1,400 W radiator at ΔT50 and specifies 55/45/20°C. At the Softline factor 0.515 the estimate is 721 W. Leave the heat-loss field blank until the surveyor supplies it. If the confirmed loss is 650 W, the margin is 71 W. If it is 850 W, the same radiator is 129 W short.
A question you can send to the installer
For the bedroom, what room temperature and outdoor design temperature did you use, what is the calculated heat loss in watts, and what output does the proposed or retained radiator deliver at the quote’s flow and return temperatures?
Check the replacement schedule for the model, size and output basis. For multiple radiators serving one room, add their outputs only after all have been expressed at the same operating conditions. Copy the combined result into the worksheet.