What does a 2,000 W radiator give at ΔT30?
Convert a catalogue rating to design output and compare it with a 1,200 W room heat loss.
Read the rating conditions
A radiator advertised at 2,000 W at ΔT50 has that rating at a mean water temperature 50°C above its test room temperature. A heat-pump design often proposes a lower temperature difference. The wattage used in the room schedule has to reflect the quoted conditions.
Mean water temperature is (55 + 45) ÷ 2 = 50°C. Subtract the room’s 20°C to get ΔT30. The Stelrad Softline brochure factor at this point is 0.515, giving 2,000 × 0.515 = 1,030 W.
Compare that with the living room
If the room design heat loss is 1,200 W, the calculated 1,030 W leaves a 170 W shortfall. To meet 1,200 W at exactly these assumptions using the same factor, the combined catalogue output has to reach approximately 2,331 W at ΔT50. Round up to an actual available product with verified design output.
Where the installer specifies a different product or quotes watts already corrected to ΔT30, ask for that product’s test data. Enter an already corrected figure as “Installer’s output at design temperatures”. A second multiplication would reduce it incorrectly.
Compare your quotes