Compare radiator quotes room by room
Check whether each quoted radiator covers the room’s heat loss at the flow and return temperatures your installer proposes.
Compare your quotes
Room-by-room radiator comparison
Enter each installer’s temperatures and the figures they supplied for the same room. Keep a missing figure blank. The living room is a worked example you can edit.
Quote guides
What does a 2,000 W radiator give at ΔT30?
Convert a catalogue rating to design output and compare it with a 1,200 W room heat loss.
Compare two radiator schedules for the same room
See how two quotes can match on the front page and disagree in the living room or bedroom.
What to ask when a room heat loss is missing
Find the missing value in a quote and give the installer a question they can answer.
Flow, return and room temperature explained
Work from the temperatures on a quote to a published correction factor or a clearly marked estimate.
Which correction factor applies?
For Softline, the calculator uses the table in Stelrad’s August 2022 brochure, printed page 74. At ΔT30 its factor is 0.515. The separate Stelrad Professional table lists 0.513. Match the table to the product in your quote. Cast Iron Radiator Centre publishes factors for its own radiators from ΔT20–60. Between published rows the calculator labels a straight-line estimate. Other products need a verified design output from the installer. Catalogue input may be in watts or BTU/h (1 W ≈ 3.41214 BTU/h).