Flow, return and room temperature explained
Work from the temperatures on a quote to a published correction factor or a clearly marked estimate.
Two temperature differences appear on a quote
The difference from flow to return describes the water cooling across the circuit. The radiator output table instead uses the difference between the mean water temperature and the room. For a 55°C flow and 45°C return, the water drop is 10°C. In a 20°C room the radiator table lookup is ΔT30.
What changes at 50/45/20°C?
The mean is 47.5°C and the radiator temperature difference is 27.5°C. The Softline brochure gives 0.406 at ΔT25 and 0.515 at ΔT30. Linear interpolation halfway between the two gives 0.4605. A 2,000 W panel would yield an estimated 921 W. An exact manufacturer figure for the actual model and design point takes precedence.
Use one design point for a fair comparison
If an installer uses 55/45/20°C and the second uses 50/45/20°C, an identical 2,000 W Softline would appear as 1,030 W and an estimated 921 W. The optional common-temperature view shows both emitters at one set of conditions. It compares output alone because a change in the intended room temperature also affects the heat-loss calculation.
Where the worksheet stops
The brochure table spans ΔT20 to ΔT65. At 40/35/20°C the result would require ΔT17.5, outside that range. The calculator asks for the installer’s output instead of extrapolating. For Cast Iron Radiator Centre’s cast iron range, the published table stops at ΔT60. Fan-assisted emitters and other radiator families can have different performance curves. Request their own data.
Flow must exceed return and return must exceed the room setpoint for the water-temperature comparison used here. If the printed figures do not meet those conditions, check the units and design assumptions with the installer.